Abstract

In the practical application of indoor air quality assurance system, it is difficult to detect the fault of air valves, CO2 sensors and other components, resulting in substandard air quality and increased energy consumption. In this paper, 16 fault conditions and 1 no fault condition were simulated by Simulink simulation software for primary return air conditioning system in summer, and a typical indoor air quality assurance system simulation fault characteristic table was obtained. It is found that PM2.5 sensor fault mainly affects indoor PM2.5 purification speed. The fault of a CO2 sensor affects indoor CO2 dilution and system energy consumption. Small resistance of return air valve increases system energy consumption. Small resistance of supply air valve, exhaust air valve and return air valve decreases the system's ability to control indoor pollutants.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call