Abstract

After power delivery grid splitting off from the main power grid, there is the risk of over frequency generator tripping leading to low frequency load shedding action. Regulation characteristic of hydro-turbine speed control system for regional power grid is analyzed by using the measured parameters of hydropower. The turbine speed control effect is analyzed without lower limit of primary frequency regulation. Frequency control improvement program of hydropower generating units in isolated power system is proposed based on wide area measurement system. The scheme uses WAMS to collect power information as governor PID output lead, and to calculate power target into the speed control system.