Abstract

As an important electrical connection component in electrical equipment, the strap contact is directly related to the long-term operation stability of equipment. The electrical contact resistance (ECR) of the electrical connection structure is an important indicator for evaluating the reliability of the electrical contact system. In this research, the theoretical calculation of ECR of the strap contacts used by the G-W theoretical model and the fractal theoretical model is improved and compared. After comparison with the experimental measurement values, the rationality and accuracy of the two theoretical models are discussed. The results show that when the load is small (1–3 N), the maximum error of G-W model is 41%, while the fractal model method has a maximum error of 9%. When the load is large (4–10 N), the results of the two are almost the same, and the errors are both within 14%. In summary, the error range of the fractal model is smaller and the change trend is closer to the experimental value, which is suitable for a relatively better ECR analytical calculation theory. The research results can provide a theoretical basis for research on the electrical contact performance of the electrical contact structure of electrical equipment.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call