In this paper, through the analysis of an electromagnetic Potential Transformer (PT) fuse fault in the distribution network, it is found that the cause of this type of fault is the low-frequency oscillation and inrush current of the voltage transformer caused by the disturbance, and its occurrence mechanism is studied and explained. After analyzing the advantages and disadvantages of the common PT fuse-blowing fault control measures, this paper proposes a treatment plan for the PT neutral point to suppress the fuse blowing through a nonlinear flow-sensitive harmonic elimination device. The harmonic device has a remarkable suppression effect on the PT fuse blown fault.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.