Abstract
The existing system of partial discharge location in substation utilizes Omni-directional UHF sensors array which can achieve single-source partial discharge source location. But for multi-source UHF partial discharge signals, the system is inaccurate and can’t distinguish types of partial discharge. This paper proposed to the method multi-source partial discharge signals acquisition and separation based on different characteristics of different types of UHF partial discharge signals in the time domain and frequency domain. Through continuously collected and stored UHF partial discharge pulse waveform, the sampling pulse sequence is analyzed in time-frequency domain to extract characteristic parameters. And then using fuzzy cluster, it can distinguish multi-source UHF partial discharge signals and discharge signals generated by the interference to achieve multi-source UHF partial discharge signals location. And it can lay the foundation of identification of the type of partial discharge. Field tests show that the method is feasible.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.