Abstract
In nuclear fusion power supply systems, the thyristors often need to be connected in parallel for sustaining large current. However, research on the reverse recovery transient of parallel thyristors has not been reported yet. When several thyristors are connected in parallel, they cannot turn-off at the same moment, and thus the turn-off model based on a single thyristor is no longer suitable. In this paper, an analysis is presented for the reverse recovery transient of parallel thyristors. Parallel thyristors can be assumed as one virtual thyristor so that the reverse recovery current can be modeled by an exponential function. Through equivalent transformation of the rectifier circuit, the commutating over-voltage can be calculated based on Kirchhoff's equation. The reverse recovery current and commutation over-voltage waveforms are measured on an experiment platform for a high power rectifier supply. From the measurement results, it is concluded that the modeling method is acceptable.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.