Abstract

The wireless private network carrying power business is a research hotspot in recent years. This paper researches the frame loss problem when 1.8GHz TD-LTE wireless private network carries power services, and studies a UDP power control system model based on 1.8GHz TD-LTE wireless private network communication, statistics the frame loss rate of power UDP control service when using wireless private network communication, analyzes the cause of frame loss problem, and proposes an optimization scheme of reducing data traffic of the control service and transmitting redundant packets at application layer to solve the problem of unstable reliability of power control services. The network tester IXIAXM2 is used to build the simulation experiment environment. The optimization method can effectively reduce the frame loss rate of the power control services based on wireless private network and improve the load-shedding success rate of the load control system, and reduce the impact of frame loss on power control services, thereby improving the reliability of the power control business.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.