Abstract

In recent years, underground pipe gallery has become more and more important. Its Special working environment makes temperature monitoring and control increasingly important. paper applies heat-transfer differential equation to the cable to obtain the similarity criterion of cable temperature distribution. After calculating the electric cabin model with different fire separations, it is found that the temperature distribution of the same ampacity in different fire separations conforms to certain rules. The temperature distribution of different ampacity in the same fire separation is also regular: the ampacity rises. 5%, temperature rises by 7%. As a result, the fitting formulas of the current carrying capacity, the length of the fire separation and the location of the highest temperature were also proposed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.