Abstract
Pressure monitoring technology is the current state monitoring research hotspot of oil-less power equipment. Aiming at the lack of pressure change characteristics caused by overheating insulation defect of oil-less power equipment, this paper studies the pressure change characteristics of 110kV oil-immersed power transformer under local overheating insulation defect. Overheating defect belongs to the low temperature overheating, temperature rise gradient is 50 °C . Analysis of the experimental results indicates that pressure change trends show exponential, in the initial stage, the pressure increased sharply, then it increased slowly, and finally it tended to be stable; the increase of pressure in 50 hours ranged from 1kPa to 3kPa, and the pressure increase was obvious, which indicated that the online monitoring of local overheating insulation defects of the casing could be achieved by pressure monitoring technology, and finally the casing pressure change law was analyzed theoretically.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.