Abstract

In tension stringing construction, the conductor defects of loose strand often occur, which affects the construction quality and conductor life. There is no suitable method to express the physical state of such loose strand at present. Through the study of the loose strands section of the conductor, the physical model of the loose strands of the conductor is established, and the physical calculation formula of scattered strands and lantern included in loose strands defect is proposed, as well as the discrimination coefficient of the scattered strands k 1 and the lantern k 2 . 3D scanning technology of industrial CT was used to scan and model the loose strand samples of JL/G1A-630/45-45/7 and JL1/G2A-1250/100-84/19 ACSR obtained from the loose strand reproduction test of conductor. The CT scanning model is evenly intercepted to measure multiple sections, and the scattered strands coefficient and the lantern coefficient are calculated. The results show that: When k 1 and k 2 ≥ 1.2, the scattered strands and lantern defects of the conductor are more obvious, which can be used as a criterion.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.