Abstract

A heat pump-based mine solution dehumidification and cooling system is used in deep mines, which can not only reduce the temperature and humidity of the working face, but also recycle the low-grade heat energy and improve the utilization rate of energy.Under the condition of long distance air supply, within the range of 10m from the heading face, the equivalent temperature of the air can fall to 24.7 °C, the cooling range is 5.6 °C, and the relative humidity decreases by 23.79%. Compared with the original cooling system, the COP value of the system can reach 3.43 under the same working conditions, 19% higher than the original cooling equipment.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.