Abstract

With the rapid development of power systems, the switchgear, which is widely used, plays an increasingly important role. Partial discharge is one of the main causes of insulation failure of the switchgear, which is a serious threat to personal and equipment safety. In this paper, the partial discharge of the switchgear is detected based on the ultrasonic method. According to the characteristics of ultrasonic waves generated by partial discharge, a partial discharge detection method for the switchgear based on the characteristics of ultrasonic wave signal is designed. The wavelet threshold denoising algorithm is used to denoise the ultrasonic signal and draw the partial discharge phase distribution map by using the characteristics of low amplitude and wide frequency distribution of the interference signal. Finally, the improved support vector machine algorithm is used to identify and diagnose four types of discharge based on 280 groups of experimental data. By adjusting the kernel function and optimizing the support vector machine algorithm, the final recognition accuracy is more than 90%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.