Abstract

Diamond nitrogen-vacancy (NV) center has been widely employed in experimental magnetic field measurement using continuous wave optical detection magnetic resonance (ODMR), which makes it possible for current sensing. An optical fiber current transducer prototype using an NV center is built for electric power application. The DC measurement with an error of less than 4% within 500 A is realized, in which the error of 50 A to 450 A is better than 2%, and the low-frequency AC measurement is preliminarily realized. In this essay, the accuracy of low current measurement is primarily affected by system noise, while the accuracy of heavy current is mainly affected by the width of the ODMR resonance peak. Optimizing the optical path as well as sensing structure meanwhile updating the demodulation algorithm of the measured data is the following work to improve the measurement accuracy.