In this paper, a new blast and fire stopping system of valve hall for UHVDC converter station is proposed. With the hydrocarbon temperature rise curve, the fire resistance test of a 1.4m×1.8m sample was carried out, a numerical model for blast resistant analysis of the firestop structure was established, and the blast resistant performances of the original firestop structure and the new structure were calculated. The results show that the new fire and blast stopping system proposed in this paper has a fire endurance time limit of more than 4 hours with the hydrocarbon heating curve. At the same time, compared with the original system, the blast resistant capability of the new firestop structure is greatly improved.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.