Abstract

For medium voltage islanding microgrid, the voltage clamp of the main network neutral arc suppression coil or small resistance is lost. Multiple PTs parallel operation will occur because different entities of a microgrid independently measure the voltage. It is necessary to consider the influence of multi PTs ferroresonance on the neutral grounding mode of islanding microgrid. The neutral point ungrounded, neutral point grounded by arc suppression coil and neutral point grounded by small resistance are analyzed respectively, considering multi PTs ferroresonance and single-phase earth fault location, it is determined that the islanded microgrid adopts neutral point grounded by small resistance. On this basis, the zero sequence current distribution is used to locate the single-phase earth fault. Finally, a simulation example is built to verify the correctness of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.