Abstract

Due to the windings of zero sequence filter are linked with zigzag connection, the zero sequence leakage reactance is the key parameter that affects the effect of the zero sequence filter. The simulation of two-dimensional leakage magnetic field in one phase of 100kVA zero sequence filter were implemented by using finite element analysis software-ANSYS, through pre-processing, solving and post-processing, the distribution of the magnetic field in the core of the zero sequence filter, the leakage magnetic field distribution between iron core and winding and the leakage magnetic field distribution between internal and external windings were obtained, then the zero sequence leakage reactance was calculated by the magnetic field energy method. This analysis provides a new idea of reducing the short-circuit impedance of zero-sequence filter and improving the filtering effect, and it can achieve purposes of shortening the design cycle and saving design cost.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.