Abstract

The electrical insulation design is important for high-Tc superconducting (HTS) cable because the cable is operated in a medium voltage environment. For the insulation design of HTS cable, it is necessary to investigate the ac, impulse breakdown, and partial discharge inception stress of a liquid nitrogen/polypropylene laminated paper composite insulation system. These results were used to design the electrical insulation of 22.9-kV-class HTS cable in Korea and cable was manufactured. A manufactured mini-model HTS cable was evaluated for ac withstand voltage, impulse withstand voltage, breakdown and dielectric tangent loss (tan/spl delta/). From these tests, the cable has satisfied the standard technical specification of KEPCO in Korea. The breakdown voltage was 110 kV.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.