Abstract
In view of energy consumption characteristics of a typical industrial park, to further improve the low-grade waste heat utilization of CCHP system, an improved CCHP triple-generation system (ITRI) equipped with thermal storage device (TSD) and electric chiller (EC) is proposed. A comprehensive performance evaluation criterion (CPEC) is established, the capacity of triple-generation system is configured by using nonlinear programming method. A hybrid operating mode optimization strategy is proposed based on the different CPEC values of different operating mode. The results demonstrate that: after adopting ITRI, compared with traditional triple-generation system (TTRI), although annual cost increased by 0.63%, the primary energy consumption rate and lower carbon dioxide emissions decreased by 5.45% and 3.72% respectively, CPEC value increased by 19.7%. This paper has a theoretical guidance for design of triple-generation system in new industrial park and has a certain reference value for operating mode optimization of triple-generation system in the industrial parks which has been built.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.