Abstract

In the actual power system with hydropower, long-time and ultra-low frequency oscillation events occur many times. It is found that the unreasonable setting of governor parameters is an important reason for the oscillation. Firstly, the single machine on load system model is used to analyse the relationship between the PID parameters of the governor and the system stability, then the relationship between oscillation mode and PID parameters of governor is analyzed by eigenvalue analysis method, and the negative damping provided by speed regulation system is analyzed by damping torque method, and then the particle swarm optimization algorithm is used to optimize the PID parameters. Through the analysis of the step response of the single machine system before and after the optimization and the damping torque coefficient provided by the speed regulation system, it shows the effectiveness of the optimization algorithm. Finally, in the simulation platform MATLAB/SIMULINK, a single machine load system model which is closer to the actual power grid is built. The governor parameters of the generator are simulated and verified, and the PID parameters are adjusted by using the parameters obtained by the optimization algorithm. The results show that the optimized parameters have a good suppression for the ultra-low frequency oscillation.