Abstract

A dynamic evaporator model of air source heat pump (ASHP), considering the ratio of the latent heat to sensible heat of wet air, is presented to analyze the performance of ASHP under frosting. The performance parameters, such as the heating capacity, COP and the outlet temperature of compressor, are simulated with CYCLEPAD. Then a semi-empirical correlation that predicts frost accumulation on the air-side of fin-tube heat exchanger is developed with dimensionless analysis and also modified by a test conducted under cold-moist conditions in winter. In addition, eight influence factors are considered involving the ambient conditions and structures of heat exchanger, whose effects are analyzed as well. Among them, the equivalent diameter of air flow cross-section in fin-tube deq is especially proposed. Lastly, the relationships between the ratio, the performance parameters and the frost accumulation are discussed in this paper, followed by an evaluation of an optimal defrosting time interval to improve the ASHP’s energy efficiency and operational reliability at cold-moist conditions in central-south China.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.