Abstract

The problem that negative sequence component of dc-link voltage will produce second oscillation under grid asymmetric faults for direct driven wind turbine with permanent magnet synchronous generator (D-PMSG) has been paid more attentions in recent years. In this paper, a new control strategy to eliminate the influence of negative sequence component to dc-link voltage is proposed by delaying 60° for the single-phase voltage to construct balanced three-phase voltage. The current feed forward is applied to inner loop, while the voltage control is used to outer loop for grid-side converter, where the dc-link voltage is stabilized. The power congestion on dc side of D-PMSG under grid asymmetric faults is solved by using the energy discharge circuit. Besides, the improved minimum energy compensation strategy is embed into the dynamic voltage restorer, which can provide the maximum reactive power support for system and compensate the faulty line voltage. The effectiveness of the proposed control method is verified by simulation results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.