For suppress the amplitude of overvoltage from HVDC sending terminal, an overvoltage suppression scheme based on the principle of controllable energy dissipation was proposed. The overvoltage mechanism of a weak AC system under the fault of the DC system was analyzed, and the method and operating principle of the CSREDD were proposed. Prototype of the develop CSREDD was tested, which proved correctness about the design. The controllable energy dissipation device has been successfully applied to the ±800kV Lu-Gu UHVDC transmission project. The operation results show that the controllable energy dissipation device can effectively suppress the AC overvoltage.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.