Abstract

Aiming at the error of calibration system when conducting field calibration by electronic DC current transformer’s digital calibration system, an electronic DC current transformer’s digital calibration system based on protocol conversion is proposed and researched. Data frames outputted from merging unit are collected and converted by the system, the digital synchronization is realized by using the synchronous clock device to trigger the second pulse, and it is verified by the virtual instrument design software. The field calibration is conducted to some converter station digital dc current transformer under the rated current of 500A by using the calibration system. By calibrating and analyzing errors, the error is less than 0.075% when tested current is more than 40% of the rated current. According the standard in literature[1], performance of the calibration system is perfect, measured results perfectly meet the requirements of design, and the calibration system has great practical application value.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call