Abstract

Aiming at the problem that how to make use of mixed data of PMU(Phasor Measurement Unit) and SCADA (Supervisory Control and Data Acquisition) to improve the traditional state estimation in power system, a new method to solve the compatibility problem of PMU/SCADA mixed data is proposed. Firstly, the differences between PMU and SCADA are analyzed, and the model of PMU/SCADA mixed data is built. We can conclude that time synchronization and measure weights are the main factors which affect the compatibility of mixed data. Therefore, data relevance analysis is used to implement the synchronization of PMU and SCADA data, and the measure weights are re-quantified by considering the delay distribution of measure data. The simulation results of ship integrated power system show the accuracy of compatibility analysis and the validity of compatibility method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.