Abstract

When the Modular Multilevel Converter (MMC) fails on the AC side, the operating characteristics of MMC will be damaged. If the system wants to retain stable for a long time in the process of operation, it is obliged to design the control strategy in case of asymmetric fault. In this article, the control strategy based on feedback linearization principle is adopted to diminish the negative sequence current caused by breakdown, and a DC voltage controller is devised to suppress the fluctuation of the double frequency component under asymmetric fault conditions. The validity of the control strategy requires to be verified, the running results on PSCAD platform indicate this method is effective and feasible.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.