Abstract

The abrupt dip of grid voltage would provoke a series of electromagnetic transient processes in stator and rotor of DFIG, which would threat the security of wind turbines fault ride through (LVRT) and stable operation of power system. Analyzing the fault current characteristics of DFIG is very useful to improve the LVRT strategy and adjust the relay protection setting of power system. In this paper, electromagnetic transient processes of DFIG are given a detail analysis after protection circuit of DFIG works due to the dip of three phase voltage in system. Then, the general expression of stator and rotor fault current is derived, and the validity of this method is verified. At last, the influences of the system short-circuit capacity and wind turbines accessing capacity on the fault current and system protections are analyzed when the wind turbines are accessed to the distribution network.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.