Abstract
With the voltage levels and capacity of UHVDC system increasing, synchronous condensers are installed in converter station to provide subtransient and transient voltage support, also it’s required to consider the demand of steady-state reactive power. Therefore the automatic voltage control (AVC) system plays a vital role in the operation and function of synchronous condenser. In this paper, taking a receiving-end condenser station for example, the overview of AVC substation is introduced, then the control strategy and switching logic between different working modes are analyzed using experimental data. Finally the impedance between the station bus and infinite power system is derived, and a method to calculate the maximum regulating value of bus voltage by synchronous condensers under steady state is proposed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.