Abstract

The insulator has an ice flashover failure. To reduce the calculation error of the equivalent icing thickness of transmission lines due to the insufficient number of sensors, a new online monitoring device for wire icing based on 3 sets of force sensors and inclination sensors was designed. The device integrates multiple monitoring functions such as micro-meteorology, wire temperature, distributed multi-rod tension, and images. The study found that the main reason for the ice flash of insulators is that the ice bridging the insulation on the string skirt. The high conductivity of melting ice water causes the ice flash voltage to be too low. A water curtain that blocks the melted ice water with high conductivity from forming a flashover channel. It is a basic measure to improve the ice-coated insulation and the flashover voltage of the ice string.