Abstract

Power cable is one of the most widely used electrical equipment in distribution system. Due to some historical reasons, the accidents such as cut or damage cables during construction often occur. In this paper, the calculation model of power cable power frequency magnetic field under different laying conditions is established. Based on the analysis of magnetic flux density around power cable, a positioning method of underground cable based on electromagnetic method is proposed. Three horizontal magnetic field sensors are used to locate the path of the cable,two vertical magnetic field sensors are used to locate the depth of the cable, so as to realize the three-dimensional positioning of the power cable. The simulation results of MATLAB show that the average absolute error of the method is about 0.03 m when the sensor array is 0.35 m around the cable in path positioning, and it can accurately locate the location of underground cable in depth location.