Abstract
To avoid the adverse effect of current transform (CT) transient saturation, this paper studies a novel bus protection based on transient current traveling-waves. Firstly the paper presents the differential traveling-wave (DTW) for each phase of circuits connected to the protected bus. The DTW fault features are analyzed. Then in order to distinguish more sensitively between faults internal and external to the bus, the restraint traveling-wave is introduced into the DTW. Thus the paper proposes the bus protection of differential traveling-waves with the restraint characteristic, and advances the practicable protection algorithm using the wavelet transform. The theoretical analysis and EMTP simulation tests show that the bus protection operates rapidly, sensitively and reliably, and that its performance can endure the influences of various fault path resistances, fault inception angles, fault locations and fault types
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.