Abstract

The Multicolumn Envelope Meshing Pair (MEMP) was proposed and has been applied for the single screw refrigeration compressor (SSRC) to reduce the wear of the meshing pair. However, the geometric model shows its changed shape of the leakage paths compared with the existing straight line envelope meshing pair (LEMP). It is necessary to research the leakage characteristics of the SSRC with MEMP and LEMP, to evaluate the value of the proposed MEMP. In this paper, the geometric model of the leakage paths between star-wheel and screw rotor is established. A two-phase leakage mathematical model for gas-oil flow is presented to predict the gas leakage rate of the SSRC with MEMP. The experiments of the performance of a SSRC with MEMP were conducted to verify the leakage mathematical model. Obtained results show the leakage of the SSRC with MEMP is a little bit smaller than that of the SSRC with LEMP.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.