Abstract

The general method to investigate the impedance characteristics with a network analyzer is discussed. The common properties of the impedance are studied based on two-months observation of two 10-kV medium-voltage power networks. Meanwhile, the difference of the impedance measured at the headside and tailside of a feeder, the impedance characteristic impacted by the operating mode of the power system, the time variance of the impedance, and the characteristic obtained from a different coupling mode are also studied carefully. The results show that the characteristic impedance is in correlation with the power system structure and its configurations, and its value is about several tenths of ohms. The input impedance varies scarcely with the time. The capacitor group connected to the bus has no influence on the input impedance. And the input impedances in common mode and differential mode are both symmetric. The impedance value in differential-mode coupling is higher than that in common-mode coupling

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.