In order to improve the Low Voltage Ride through (LVRT) level of the low voltage auxiliary frequency converter in the thermal power plant and effectively solve problems including the inaccurate drop time of voltage drop device, which is controlled by the switching structure of the traditional multi-winding transformer, excessive magnetizing inrush current occurs during the closing process, and the 30KW testing device for LVRT of the frequency converter in the thermal power plant is developed. It is designed with a three-phase four-wire back-to-back power electronic topology, together with adaptive fuzzy PI control algorithm. They can precisely set the voltage drop amplitude and time, ensuring automatic periodic cycle test controlled by upper computer. A LVRT field experiment has been carried out on low-voltage auxiliary frequency converter both before and after the transformation in a thermal power plant in Jiangxi Province. It proves that the dynamic response time of the power electronic voltage drop device is less than 5ms, the harmonic content in the converter voltage output is less than 0.5%. Additionally, the device boasts convenient operation and well-developed protection mechanism.