Abstract
AbstractWe investigated the required limiting impedance and capacity of a fault current limiter (FCL) installed at an incoming feeder of a customer system with a synchronous generator in a utility distribution system. It was assumed that two types of FCL were installed, i.e. a resistive type (R‐type) FCL and an inductive type (L‐type) FCL. A fault current out of the customer system and a voltage in the customer system were calculated following a three‐phase, short‐circuit fault occurrence. It was found that the required type of FCL and the required limiting impedance depended on the rated capacity of the generator in order to obtain the suppression of the fault current under 0.1 kAS and to maintain of customer voltage between 85 and 100% of the nominal voltage (6.6 kV). The capacity of FCL consisting of the smallest limiting impedance is discussed. © 2006 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEJ Transactions on Electrical and Electronic Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.