Abstract

This report documents the details of the Programmable Logic Controller (PLC) and the Data Table Access Module (DTAM) logic developed for the new pumping system employed for saltwell pumping. The new system is planned first for pumping A-101 where Pumping Instrumentation and Control (PIC) skid ''F'' is located. The new pump requires a bump start under certain conditions that will be controlled by the PLC. The bump start is to ensure sufficient water to the pump bearing cavities. The PLC logic is required to control the shutdown of the injection pump that supplies the water to the saltwell pump bearing cavities. Allowance to start and stop the injection pump will be controlled by the PLC at the PIC skid. This report is written for PIC skid ''P'', but will apply to other PIC skids where the new pumping system is deployed. The logic will remain the same, but the ladder rung-numbers may change from skid to skid.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.