Abstract
The UHF radiation field generated by corona discharge of the two 500kV AC transmission lines was tested. The influencing factors of radiation field, including climate, bundle conductors number and test distance, were analyzed. Test results indicate that the field continuously arranges from 200MHz to 700MHz, mainly from 200MHz to 500MHz. The maximal measurement distance is 300 meters. The climate and bundled conductors number affect the radiation field obviously. The discharge will become intense when the temperature and humidity increase and bundle conductors number decays. The peak values of the electric field strength which decay rapidly with the distance increasing, can arrive several hundreds uV/m. The test results rich the UHF radiation field data and offer references to testing and evaluating the electromagnetic interference generated by corona discharge of ultra-high voltage transmission lines.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.