Abstract

The reluctance network model of non-salient pole generator is presented, and the generator status differential equations are developed, whose parameters are stator winding branch current, stator reluctance, rotor reluctance, air-gap reluctance, rotor magnetomotive force. Its main advantages are to take into the rotor movement and saturation effects, with a good compromise between calculation time and accuracy of results. Then the rotor winding inter-turn short circuit fault is analyzed based on the model, the results show that even harmonic current will emerge in the stator winding parallel branches when the fault has happened. Finally, practically acquires data on the spot of SDF-9 type generator, the results of verification show that the theory analysis is right

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.