Abstract

The reliability of ASDs has improved very much. The resulting MTBF from realistic estimation (which is 44 years) shows an MTBF for standard LV drives that will be acceptable for most applications in the chemical industry where programs such as Improve Reliability, Equipment Justification and Minimization, and Risk-Based Engineering are common. The highest effect in improving the MTBF lays in optimizing the engineering and failure response with respect to thermal overload trips. There is still one more remark to make on reliability. The problem with frequency converters, in situations where production losses and repair costs are very high, such as fans for a furnace, is the inability to monitor the electronics and smoothly shut down the plant before trip occurs. Mechanical equipment, such as a gearbox with all available vibration monitoring techniques, should still have an advantage in these cases.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.