Abstract

In this paper, the Time-varying Failure Rates(TFR) of power distribution system components are extracted from the recorded failure data of KEPCO(Korea Electric Power Corporation) and the reliability of power distribution system is evaluated using Mean Failure Rate(MFR) and TFR. The TFR is approximated to bathtub curve using the exponential and Weibull distribution function. In addition, Kaplan-Meier estimation is applied to TFR extraction because of incomplete failure data of KEPCO. Also the reliability of the real power distribution system of Korea is evaluated using the MFR and TFR extracted from real failure data, respectively and the results of each case are compared with each other. As a result, it is proved that the reliability evaluation using the TFR is more realistic than MFR. In addition, it is presented that the application method at power distribution system maintenance and repair using the result of TFR.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.