Abstract

The authors present the evaluation of the probability and frequency of failure for a system of two parallel redundant transmission lines with common mode failure. The component down times are assumed to follow an overdispersed Gamma distribution. The two system models are presented based, respectively, on the parallel device of stages on the use of supplementary variables. The results are checked by Monte Carlo simulations. The merits of the supplementary variable model are pointed out and the relevance of the form of the distribution as well as the necessity of a careful statistical analysis of the actual failure data is addressed. It is shown that, for a Gamma distribution with shape parameter less than unity, the form of the down-time distribution can have an orders-of-magnitude effect on the probability of failure. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.