Abstract

ObjectiveThe purpose of this study was to evaluate the relationship between human plaque fibrous cap thickness detected by intravascular optical coherence tomography (OCT) and the plasma levels of inflammatory factors...

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.