Abstract

Fiber Reinforced Polymer (FRP) is commonly used in structural repair and strengthening due to its high tensile strength, non-corrosive and lightweight. On the other side FRP is relatively brittle compared to steel. This study used hybrid FRP consisting of GFRP and CFRP, by combining two type of FRP with different characteristic it is to be expected that the more brittle FRP will fail first followed by the more elastic one, therefore creating a sequential failure. However CFRP have a higher tensile strength in comparison to GFRP, therefore it’s necessary to reduce its tensile strength by reducing its volume. This study is divided into two topics, hybrid FRP tensile strength test and beam flexural test. For the hybrid FRP tensile strength test, a total of three variation of hybrid FRP will be compared (GC30, GC40, and GC50). The variation that shown a sequential failure behaviour, will then be applied to a reinforced concrete beam and tested under monotonic point load device. The test result shown that sequential failure occur on GC30 and GC40. However GC40 had a higher ultimate load at 24.86 kN. For the beam flexural test, there will be two variation, i.e. control beam (CB) and beam strengthened with hybrid FRP (BGC). When compared, BGC had a 40.0% increase in yield strength and 55.43% increase for ultimate load.