Abstract

Adsorptive media technology is frequently used by small water systems to remove arsenic because of its simplicity and efficiency. Current practice is to replace the media when it no longer reduces arsenic below the maximum contaminant level of 10 μg/L that the US Environmental Protection Agency has set for drinking water. Media replacement typically accounts for approximately 80% of the total operational and maintenance costs. One potential option to reduce the cost is onsite regeneration and reuse of the media. To evaluate the regeneration option, three consecutive regeneration studies were conducted on a full-scale adsorptive media system. This article, the first of a two- part series, describes the regeneration process and its efficacy in stripping arsenic and other contaminants from exhausted media. Study results found that a three- step regeneration process of media backwash, caustic regeneration, and acid neutralization conditioning proved effective for stripping arsenic and other contaminants from the exhausted media.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.