Abstract

Adiabatic pressure drop in chevron and two styles of bumpy plate heat exchangers were investigated for vertical upward flow with R134a. Qualities ranging from sub-cooled liquid to superheated vapor were investigated. Mass fluxes ranged from 16 kg/m 2 s (for superheated vapor) to approximately 300 kg/m 2 s (for sub-cooled liquid). The pressure drop experiments were conducted for 10 °C and 20 °C inlet temperatures. A two-phase pressure drop model, based on the kinetic energy of the flow, was developed in order to relate the two-phase pressure drop data to the single-phase data. The model predicts two-phase pressure drop within 15% of experimental measurements.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.