Abstract

This paper presents experimental results from a brine-to-water heat pump used for space heating at low temperature, with a low refrigerant charge of R290 (propane). Performance and refrigerant distribution were analysed in every test condition studied. Performance results show a declared heating capacity of 9.5kW, obtaining a specific capacity (Cc) of 48.7kWrmkg−1 and a seasonal coefficient of performance of 4.01. In terms of refrigerant distribution, at the nominal point, 41.5% of the refrigerant is located in the compressor, mainly dissolved in the oil, and the rest is separated almost evenly in both heat exchangers, 23.9% in the condenser and 27.8% in the evaporator; having the lines and accessories (pneumatic-ball valves) the remaining 6.8%. Due to this fact, reducing oil solubility by heating the crankcase or increasing the superheat (SH) has a positive impact on the refrigerant charge reduction, but it also affects the coefficient of performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.