Abstract

The U-V or V-V winding connections of two single-phase distribution transformers are widely utilized in distribution systems to deliver power to various three-phase and/or single-phase loads. Such special winding connections of distribution transformers can cause three-phase voltage unbalance in distributions systems, which could also lead to unexpected trip of ground relay, extra power losses on distribution-system lines, reduced operating efficiency of induction-motor loads, etc. This paper proposes a distribution static synchronous compensator (D-STATCOM) to effectively improve the voltage unbalance of a distribution system connected with a microgrid system. The studied microgrid system contains various renewable-energy resources, a diesel-engine generator, and three distribution transformers with U-V and/or V-V winding connections. The simulation results show that the proposed D-STATCOM with the designed controller can effectively reduce voltage unbalance of the distribution system connected with the studied microgrid system when the distribution transformers have U-V and/or V-V winding connections.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.