Abstract
Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan. Design charts were applied to predict noise reduction and length of a dissipative silencer. Dissipative silencers with various punched duct porosity (14%, 30% and 40%) and sound absorbent density (80 Kg/m3 , 120 Kg/m3 , and 140 Kg/m3 ) were designed and fabricated. According to ISO9612 and ISO11820, noise level was measured before and after installing all nine test silencers at fixed workstations around the discharge side of a centrifugal fan in a manufacturing plant. On average, the noise level at the discharge side of a fan without silencer was measured to be 93.6 dBA, whereas it was significantly mitigated by 67.4 dBA to 70.1 dBA after installing all silencers. Dynamic insertion loss for a dissipative silencer with 100 cm length was predicted to be 27.9 dB, which was in agreement with experimental ones. Although, there was no significant differences between insertion loss of silencers, the one with 30% porosity and 120 Kg/m3 rock wool density had the highest insertion loss of 26.2 dBA. Dissipative silencers noticeably reduced centrifugal fan noise exposures. Increasing sound absorbent density and duct porosity up to a certain limit could probably be effective in noise reduction of dissipative silencers.
Highlights
Noise is one of the most common physical agents in work and living environment which can be accompanied with various adverse health effects such as hearing loss, communication and efficiency interferences, poor motivation, stress, fatigue, irritability, high blood pressure, and heart rate [1–3]
Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan
The noise level at the discharge side of a fan without silencer was measured to be 93.6 dBA, whereas it was significantly mitigated by 67.4 dBA to 70.1 dBA after installing all silencers
Summary
Noise is one of the most common physical agents in work and living environment which can be accompanied with various adverse health effects such as hearing loss, communication and efficiency interferences, poor motivation, stress, fatigue, irritability, high blood pressure, and heart rate [1–3]. Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.