Abstract

Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan. Design charts were applied to predict noise reduction and length of a dissipative silencer. Dissipative silencers with various punched duct porosity (14%, 30% and 40%) and sound absorbent density (80 Kg/m3 , 120 Kg/m3 , and 140 Kg/m3 ) were designed and fabricated. According to ISO9612 and ISO11820, noise level was measured before and after installing all nine test silencers at fixed workstations around the discharge side of a centrifugal fan in a manufacturing plant. On average, the noise level at the discharge side of a fan without silencer was measured to be 93.6 dBA, whereas it was significantly mitigated by 67.4 dBA to 70.1 dBA after installing all silencers. Dynamic insertion loss for a dissipative silencer with 100 cm length was predicted to be 27.9 dB, which was in agreement with experimental ones. Although, there was no significant differences between insertion loss of silencers, the one with 30% porosity and 120 Kg/m3 rock wool density had the highest insertion loss of 26.2 dBA. Dissipative silencers noticeably reduced centrifugal fan noise exposures. Increasing sound absorbent density and duct porosity up to a certain limit could probably be effective in noise reduction of dissipative silencers.

Highlights

  • Noise is one of the most common physical agents in work and living environment which can be accompanied with various adverse health effects such as hearing loss, communication and efficiency interferences, poor motivation, stress, fatigue, irritability, high blood pressure, and heart rate [1–3]

  • Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan

  • The noise level at the discharge side of a fan without silencer was measured to be 93.6 dBA, whereas it was significantly mitigated by 67.4 dBA to 70.1 dBA after installing all silencers

Read more

Summary

Introduction

Noise is one of the most common physical agents in work and living environment which can be accompanied with various adverse health effects such as hearing loss, communication and efficiency interferences, poor motivation, stress, fatigue, irritability, high blood pressure, and heart rate [1–3]. Acoustic performance of dissipative silencer was evaluated to determine the effectiveness of perforated duct porosity and absorbent material density in reducing occupational noise exposure propagated from centrifugal fan.

Results
Conclusion