Abstract

This paper investigates a reduced switch count dc-link ac–ac five-leg converter for three-phase power conversion. The converter provides both an input rectifier and an output inverter by sharing a leg in order to reduce the number of power switches. Scalar and vector pulsewidth modulation techniques are presented and the concepts of local and global apportioning factors are introduced. A control technique that aims at maximizing the utilization of the dc-link voltage is proposed. A hysteresis current controller that allows operating with one leg being shared by the load and grid sides is developed. In addition, several relevant characteristics of the converter are addressed, such as voltage capability, harmonic distortion, shared-leg and capacitor currents, and power rating. The features of such a converter are compared to those of the six-leg and four-leg converters. Selected experimental results are presented.