Abstract

Recovery time of Bi-2223/Ag HTS tapes after quench by short-time AC over-current has been observed. The experiment is carried out using an electromagnetic switching circuit. In order to confirm the state of the tape, a small DC current is fed continuously to the tape. The HTS tape is immersed in liquid nitrogen bath. The duration of the over-current is about 100-200 ms (5-10 cycles in 50 Hz), and the magnitude of the transient AC current is 150 A which is about 3 times larger than the DC critical current of the tape. The experimental result shows that the normal voltage generated by the over-current disappears about 2 ms after the end of the over-current. In addition to the experiment on HTS tapes, an experiment on a HTS coil wound by Bi-2223/Ag HTS tape is carried out. Also from this experiment good superconducting-to-normal-conducting recovery characteristics are confirmed. These experimental results will encourage the possibility of many applications of HTS tapes to power apparatus.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.