Abstract

This two-part paper presents an inverse method to reconstruct the primary voltage of a VT from the available distorted secondary signals. In this second part, the performance of the proposed inverse method is validated by simulation using a 10 kV inductive voltage transformer (VT). Additionally, four laboratory experiments are performed to show the potential applications of the proposed method. These experiments closely represent realistic field conditions. The simulation and experimental results verify the accuracy and reliability of the method. The robustness and parameter accessibility are discussed. The novel inverse method provides an effective solution for the accurate reproduction of high-frequency transients and low-frequency over-voltages measurements. Furthermore, the reconstructed primary voltage waveforms provide usable data for the study of voltages in power systems.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.